  • Saturday, April 21, 2018 2:15 AM
    Reply # 6113461 on 6109711

     Booms are not considered surgical instruments. 

  • Sunday, April 22, 2018 10:39 AM
    Reply # 6114400 on 6109711
    Al Moon (Administrator)

    Just a word of caution !


    Yes the cause and effect:


    In regards to the reduction of the IA system receiver pressure 

    (original listed as 200 psig) and the final line pressure (still in table 5.1.11 listed as 169-185 psig) for a Instrument Air ( IA ) Medical Support Gas.


    The NFPA 99 Edition 2018, provides a statement that allow, a reduction in the source and final line delivery pressures. In my opinion the wording is weak .


    Section 5.1.13.3.4.3 & 5.1.13.3.4.5.

    This change still refers us back to Table #5.1.11

    which has IA pressures between 160-185 psig.


    But no matter what you do / the system still has to provide the following requirements . 


    1) Quality of IA Source (i.e. up-stream of the final line regulator) 

    a pressure Dew-Point of -40 C ( -40 F)

    2) Master and Local Alarms, if the IA system delivery pressure exceeds a pressure Dew-Point of -30 C ( -22 F )


    The above is just a short listed of all the items or conditions still required.

    (see the full section #5.1.13.3.4)


    Also for those with existing IA systems with the intent of just turning down the final line pressure to less than the listed (160-185 psig), remember to replace the pressures relief valves to meeting the code.   




  • Tuesday, April 24, 2018 5:26 AM
    Reply # 6117508 on 6109711
    Deleted user

    I think Corky is right

    Using ~60 psig "Non-Medical Air" instead of Instrument Air does not require costly zone valves, area alarms, master alarms, special instrument air labels, and a very expensive source supply.  In my opinion Instrument Air is "permitted," but not "required" to be used for boom brakes, and a much less expensive Non-Medical Air system is also permitted to be used for boom brakes.

  • Tuesday, October 23, 2018 11:32 AM
    Reply # 6870096 on 6117508
    Anonymous
    Steve Bradshaw wrote:

    I think Corky is right

    Using ~60 psig "Non-Medical Air" instead of Instrument Air does not require costly zone valves, area alarms, master alarms, special instrument air labels, and a very expensive source supply.  In my opinion Instrument Air is "permitted," but not "required" to be used for boom brakes, and a much less expensive Non-Medical Air system is also permitted to be used for boom brakes.


    I agree with you Steve and Corky but it seems like most boom brakes operate @ 80psig. Maybe that's just Steris and Stryker. 