EOSC testing

  • Thursday, February 29, 2024 10:39 AM
    Message # 13322593

    I received a call today asking about functionality testing of an EOSC. While I had a conversation with the individual on my thoughts for testing, I was wondering if anyone has done that and how did they do it?  

  • Friday, March 01, 2024 7:49 AM
    Reply # 13323070 on 13322593
    Cary Darden (Administrator)

    Hi Bob, 


    We test EOSCs for proper functionality when the facility does not have good documentation showing when the last date it has been successfully used.  The main items we check for are that both check valves work properly and that the relief isn't lifting early (i.e. < 57-58 psig).  This is typically achieved by connecting an H cylinder or in some cases several H cylinders to the EOSC box with a regulator (or two depending on the demand we need to overcome from the house feed) and confirming we can raise house pressure downstream of all EOSC components 2-3 PSI over the house line pressure.  We never allow the pressure to go into the alarm state of 60 PSI, however I know of a few companies who have tested it that way and it seemed to work as a method also.  

  • Sunday, March 03, 2024 8:32 AM
    Reply # 13323909 on 13322593
    Rocky Plotts (Administrator)
    We do the same basic method as Cary. We do not do this for all of our annuals, but do offer it as an option. Many VAs we test annually have this in their SOWs. 

  • Monday, March 04, 2024 7:45 AM
    Reply # 13324257 on 13322593

    Thanks for the input, this was a request by a healthcare facility. These replies were along the line that I was thinking starting with a visual inspection and then actual functional testing. 

  • Tuesday, March 19, 2024 9:21 PM
    Reply # 13332006 on 13322593

    Suggested EOSC check valve test procedure:

    1. Open the threaded connection and ensure there is no pressure on the system at the EOSC gauge.

    2. Connect a USP 99 grade Oxygen H cylinder to the connection port of the EOSC location.

    3. Have the +1% accurate test gauge in line between the EOSC connection and the cylinder regulator for the following steps.

    3. Bring the oxygen pressure up to no greater than 4 psig above the hospital main line pressure noted on the building pressure switch DISS demand check or the closest oxygen outlet. Note the results. Did flow initiate at or just above the hospital pressure? Yes - pass. No - fail.

    4. At the high pressure leak check all hose connections, cylinder/regulator and EOSC/hose connections for leaks. Repair if possible or note of not repairable for this test.

    5. Release the oxygen pressure through the cylinder/hose assembly.

    6. Once all flow has ceased out of the EOSC location and the test gauge is at 0 psig tighten the cylinder/hose assembly (we use a 1/4" valve teed at the test gauge.

    7. Is the EOSC gauge at 0 psig and did it equal or was within it's analytical accuracy reading at the peak pressure during the test as compared to the test gauge readings?  Yes - Pass.  No - Fail.

    8. After 20 minutes observe the pressure on the test gauge connected within the EOSC location. 0 psig - pass.  >0 psig - fail.

    9. Remove the test gauge and install EOSC gauge.

    10. Reconnect Oxygen H cylinder and bring pressure to hospital pressure and leak test the EOSC location gauge. No leaks - Pass. Yes - attempt seating gauge again until a Pass is achieved.

    11. Release all oxygen pressure and cap/plug the EOSC port.

    12. Close the EOSC location cover and secure with the hospital lock.

    13. Observe labeling - meets NFPA 99, 2012? Yes - pass. No - Fail.

    14. Record results.


    I look forward to reading your comments, questions and concerns. Especially if you have another method to suggest.

    Last modified: Tuesday, March 19, 2024 9:34 PM | Carsten Lunde

16339 Kranker Drive, Stilwell, KS 66085

mgpho@me.com