Hyperbaric Exhaust Lines

  • Wednesday, September 23, 2015 3:10 PM
    Message # 3541370
    Deleted user

    Hello everyone.  Can't wait to see y'all again, but can't wait to ask you this question.


    What are the requirements for the exhaust lines for a hyperbaric chamber?

    B819, brazed and purged obviously.  But, I can't find out where it says "to the roof" or just "outside".  Then, how far away from intakes, etc.  


    Thanks and see you in KC..

  • Thursday, September 24, 2015 8:15 AM
    Reply # 3542456 on 3541370

     

    Hi Chris,

    This may not answer all the questions, but this is what can be found in NFPA 99, 2015.

     

    14.2.10.2*

    Exhaust from all classes of chambers shall be piped outside of the building.

    14.2.10.2.1

    Each Class B chamber shall have an independent exhaust line.

    14.2.10.2.2

    The point of exhaust shall not create a hazard.

    14.2.10.2.3

    The point of exhaust shall not allow reentry of gases into the building.

    14.2.10.2.4

    The point of exhaust shall be protected by the provision of a minimum of 0.3 cm (0.12 in.) mesh screen and situated to prevent the intrusion of rain, snow, or airborne debris.

    14.2.10.2.5

    The point of exhaust shall be identified as an oxygen exhaust by a sign prohibiting smoking or open flame.

    14.2.10.3

    The supply piping for all air, oxygen, or other breathing mixtures from certified commercially supplied cylinders and portable containers shall be provided with a particulate filter of 66 microns or finer.

    14.2.10.3.1

    The particulate filter shall meet the construction requirements of ANSI/ASME PVHO-1,

    Safety Standard for Pressure Vessels for Human Occupancy, and be located as close as practical to the source.

    A.14.2.10.2

    Exhaust piping extending from the building can create a lightning risk. Lightning protection should be considered.

  • Thursday, October 08, 2015 8:40 PM
    Reply # 3568125 on 3541370

    Sechrist states in their Hyperbaric Chamber Operations Manual and installation guide the exhaust shall be at least 8 feet above the finished floor of the chamber room. This guide also will identify the recommended exhaust pipe ID for the chamber.

16339 Kranker Drive, Stilwell, KS 66085

mgpho@me.com