Oxygen cylinders location

  • Thursday, December 01, 2016 4:49 PM
    Message # 4434627
    Al Moon (Administrator)

    a hospital has a helicopter pad, the pad is surrounded by a four foot chain link fence, at one corner they keep (H) tanks for storage and used. (Yes for transfilling): does my standard NFPA 99 Code apply.

  • Friday, December 02, 2016 8:17 AM
    Reply # 4435776 on 4434627

    NFPA 418 section 4.3.2, Oxygen and other medical gases shall be stored and used in accordance with NFPA 99.

    NFPA 418 section 4.3.3, Above ground flammable liquid storage tanks, compressed gas storage tanks, fuel storage tanks, and liquefied storage tanks shall be laterally located at least 50 feet from the edge of the FATO as defined in FAA AC 150/5390-2C Heliport Design Advisory.

    Confusing yes, I think you need to go with 4.3.3

  • Thursday, September 05, 2019 6:06 AM
    Reply # 7865053 on 4435776
    Robert Sutter wrote:

    NFPA 418 section 4.3.2, Oxygen and other medical gases shall be stored and used in accordance with NFPA 99.

    NFPA 418 section 4.3.3, Above ground flammable liquid storage tanks, compressed gas storage tanks, fuel storage tanks, and liquefied storage tanks shall be laterally located at least 50 feet from the edge of the FATO as defined in FAA AC 150/5390-2C Heliport Design Advisory.

    Confusing yes, I think you need to go with 4.3.3

    Rocky Plotts. Read this. 