A new replacement hospital looking to put CO2, N2, and N2O manifolds in a small room.
I was looking at requirements for mechanical ventilation, and want to use this installation to see if I am fully understanding this requirement, as I haven't had cause to use it recently.
Room to contain connected cylinders only:
24 N2 @ 255 cu' = 6120 cu'
24 N2O @ 567 cu' = 13608 cu'
12 CO2 @ 568 cu' = 6816 cu'
Total 26,544 cu' of gas in use.
9.3.6.5.3.2 Mechanical exhaust shall be at a rate of 1 CFM of airflow for each 5 cubic feet of liquid designed to be stored in the space and not less than 50 CFM nor more than 500 CFM.
26544/5 = 5308.
My understanding is that the 500 CFM max rate would apply even though gas connected is over 10X noted.
Is it correct to state that anything over 2500 cubic feet can be ventilated by a 500 CFM system?
Thanks in advance...
Bob W.