Catagory 3 Manifold cylinders

  • Wednesday, January 06, 2021 9:54 AM
    Message # 9721785
    Deleted user

    OK my question is:

    NFPA 2021 5.3.3.5.10 cylinder or liquid header. Category 3 systems shall comply with 5.1.3.5 and 5.1.3.5.9, except as follows:

    (1) Gas cylinders or cryogenic liquid container headers shall be in accordance with 5.1.3.5.9, with sufficient cylinder connections to provide for at least one average day's supply, and with the appropriate number of connections determined only after consideration of the delivery schedule..... etc. (No mention of a minimum cylinder requirement)


    However: 5.3.3.5.12: Category 3  systems shall comply with 5.1.3.5 and 5.1.3.5.10.


    5.1.3.5.10.4 (1) Two equal headers in accordance with 5.1.3.5.9 each with a sufficient number of cylinder connections  for one average day's supply but not fewer than two connections.... etc.


    So, can Category 3 facility have only one cylinder for header as per 5.3.3.5.10  or two cylinders as per 5.1.3.5.10.4(1) ?

  • Wednesday, January 06, 2021 10:29 AM
    Reply # 9722436 on 9721785
    Deleted user

    Sorry last line was wrong:

    So, can a Category 3 facility have one cylinder per header as per 5.3.3.5.10 (1) or must it have two per header as per 5.1.3.5.10.4 (1)