Take it for what it is, Annex D in ASSE 6000
D.5.5 High/Low Pressure Alarms
a) If the pressure/vacuum sensors are installed
with gas-specific demand check fittings, they
can be removed from the piping system and
individually tested using a source of test gas or
vacuum.
b) For positive pressure gases:
1) Reduce the pressure to 20% below normal.
Verify that the appropriate alarm trips.
Silence the audible alarm. The visual alarm
should remain activated.
2) Raise the pressure to normal. The visual
alarm should be deactivated.
3) Raise the pressure to 20% above normal.
Verify that the appropriate alarm trips.
Silence the audible alarm. The visual alarm
should remain activated.
4) Reduce the pressure to normal. The visual
alarm should be deactivated.
c) For vacuum alarms:
1) Decrease the vacuum from normal to 300
mm (12 in) Hg. Verify that the appropriate
alarm activates. Silence the audible alarm.
The visual alarm should remain activated.
2) Increase the vacuum to normal. The visual
alarm should be deactivated.